There are some basic requirements for air conditioning systems in operating theatres.
-
1.
Obviously the regulation of temperature and humidity is necessary, but cleaning of fresh air and circulating air is much more important.
-
2.
Concerning cleaning, a high standard of filtration of air is demanded to avoid contamination of wounds.
-
3.
So far only HEPA-filters, a technical description, give security and safety. They filter particles down to under 1 μm and have a filtration rate of more than 99.9%.
-
4.
The ventilation rate is directly related to the germ concentration in the air. The higher the ventilation rate the cleaner the air during working.
-
5.
To avoid turbulences unidirectional or uniform flow is necessary. This technique has become popular as the laminar flow technique. To get such a flow an air flow velocity of 0 45±0.1 m/s is necessary.
-
6.
The arrangement of the different working places in an operating theatre is very important. Instrument tables and the operation field itself have to be in the zone of first air.
-
7.
One of the commonest germ dispersion sources is the human body. Proper dressing and behaviour have to be observed. The airflow behind a person (in laminar cross flow) or under a person (in laminar down flow for instance when the neurosurgeon bends his head over the operating field) has to be regarded as contaminated.
-
8.
Hygienic controls must be made in the operation theatre when unused and also under working conditions, in a sophisticated manner.
If all these points are respected a real clean room technique is possible with considerable lowering of the risk of infection for the patient. Obviously all the other rules of hygiene,i.e., asepsis and antisepsis, elaborated since the days of Lister, have to be strictly respected.
Similar content being viewed by others
References
Allander, C., Abel, E., Untersuchung eines neuen Einblasesystems für Operationsräume. Dechema-Monographie Bd.69 (1968), 297–306.
Austin, P. R., Timmerman, S. W., Design and operation of clean rooms. Detroit: Business News Publ. 1965.
Botzenhardt, K., Rüden, H., Zur Beurteilung von Klimaanlagen im Krankenhaus. Klima-Kälte-Technik7 (1973), 139–143.
—, Wanner, H. U., Technik des Keimnachweises in Laminar-flow Operationsräumen. In: Sattel, W., Peiper, H. J., Reinraumtechnik, Anwendung in der Medizin, 81–88. Berlin-Heidelberg-New York: Springer. 1977.
Charnley, J., A clean-air operating enclose. Brit. J. Surg.51 (1964), 202.
Nouri, Z., Reinfeldverfahren zur Erzeugung lokaler luftkeimarmer Bereiche. Bericht anläßlich der 5. Fachtagung für Krankenhaustechnik der Medizinischen Hochschule Hannover, April 1977 (gedruckte Fassung 1978, 41–49).
Peiper, H. J., Sattel, W., Schubert, E, Verminderung der Infektionsgefahr durch Anwendung einer turbulenzarmen Verdrängungsströmung im Operationssaal. Der Chirurg45 (1974), 545–549.
Regenscheit, B., Die Archimedes-Zahl-Nennzahl zur Beurteilung von Luftströmungen. Gesundh.-Ing.91 (1970), 172.
Russenberger, H. J., Wanner, H. U., Keimgehalt der Raumluft in Abhängigkeit des Luftwechsels. Zbl. Bakt. Hyg. I. Abt. Orig. A.227 (1974), 564–567.
Sattel, W., Peiper, H. J., Reinraumtechnik. Anwendung in der Medizin. Berlin-Heidelberg-New York: Springer. 1977.
— —, Berendt, R., Auswirkung auf die Organisation in LF-Räumen und LF-Kabinen. In: Sattel, W., Peiper, H. J., Reinraumtechnik, Anwendung in der Medizin, 71–80. Berlin-Heidelberg-New York: Springer. 1977.
Schepelmann, F., Greiner, L., Pia, H. W., Complications following of herniated lumbar discs. In: Advances in neurosurgery 4 (Wüllenweber, R.,et al., ed.), pp. 52–54. Berlin-Heidelberg-New York: Springer. 1977.
Schicht, H. H., Grundlagen und Anwendungen der Reinraumtechnik. Der Gesundheitsingenieur93 (1972), 232–241.
—, Steiner, W., Klimatechnische Beiträge zur Asepsis im Operationssaal. Technische Rundschau4 (1972), 2–14.
Schütz, H., Probleme der Luftreinhaltung und -hygiene im Krankenhaus. Klima-Technik4 (1970), 12–27.
Skiba, H., Klimatisierung von Op-Räumen mit Hilfe der Reinraumtechnik. Sanitär- und Heizungstechnik1 (1975), 19–24;2 (1975), 66–72.
Stokes, E. A., Mulcaster, K. D., Air filtration. Steam and Heating Engineer10 (1969), 3.
Strauss, H. J., Strömungstechnische und luftfiltertechnische Grundlagen der LF-Reinraumtechnik. In: Sattel, W., Peiper, H. J., Reinraumtechnik, Anwendung in der Medizin, 1–33. Berlin-Heidelberg-New York: Springer. 1977.
Thomsen, K., Krebs, D., Fehlerhafte Klimaanlage infizierte Operationstrakt. Deutsches Ärzteblatt Heft10 (1972), 544.
Wanner, H. U., Bakteriologische Kontamination in konventionell belüfteten Operationssälen. Berichte Unfallmedizinische Arbeitstagung, Göttingen: 1972.
- Möglichkeiten und Grenzen der Reinraumtechnik in der Medizin. Chemische Rundschau 53–56 (1974).
Weber, B. G., Stühmer, G., Meierhans, L., Sterile Operationsboxen. Z. Orthop.109 (1971), 803.
— — —, Die Bekleidung des Operationsteams in einer sterilen Operationskabine. In: Internationales Symposium für Reinraumtechnik. Reinraumtechnik I, 132, Solothurn: Vogt-Schild. 1973.
Whitcomb, C., Technical lecture series on industry and microbial contamination control. Palo Alto/Calif.: Stanford University. 1969.
Whitfield, W. J., A new approach to clean-room design. Reprint No. SC-4673 (RR). Albuquerque/New Mexico: Sandia Corp. 1962.
Winkler, S., Roemer, G. B., Matz, K., Konstruktion und Wertung der Klimaanlagen verbessern. Deutsches Ärzteblatt Heft10 (1972), 548.
Author information
Authors and Affiliations
Rights and permissions
About this article
Cite this article
Lorenz, R. Air conditioning systems. Acta neurochir 55, 49–61 (1980). https://doi.org/10.1007/BF01808920
Issue Date:
DOI: https://doi.org/10.1007/BF01808920